Determination of fire risk level and complementary assessment of fire load in a commercial establishment

Authors

  • Carlos Daniel Cruz Rodríguez National Technological Institute of Mexico image/svg+xml
  • José Antonio Moreno Cruz Autonomous University of Tamaulipas image/svg+xml
  • María Guadalupe López Martíez Guanajuato State Virtual University image/svg+xml

DOI:

https://doi.org/10.61273/neyart.v4i4.235

Keywords:

fire risk, fire load, fire safety, NOM-002-STPS-2010

Abstract

Fire prevention in commercial establishments requires consideration of both regulatory criteria and actual operating conditions. The objective of this study was to determine the fire risk level of a commercial establishment through the application of NOM-002-STPS-2010 and to complement this assessment with a fire load estimation using engineering criteria and the   methodology as a reference. A descriptive and technical case study was conducted based on on-site information gathering, identification of combustible materials, inventory determination, and assessment of operating conditions. The establishment contained 8,000 kg of combustible solids and 430 L of Class B liquids. Application of the criteria established in Appendix A of NOM-002-STPS-2010 resulted in an Ordinary Fire Risk Level. As a complementary analysis, a potential energy of 146,600 MJ was estimated over an area of 600 m², resulting in a specific fire load of 244.33 MJ/m², considered low according to the criterion adopted. Nevertheless, operating conditions associated with electrical installations, combustible material storage, flammable liquid handling, and possible obstruction of evacuation routes were identified. The results show that compliance with regulatory classification parameters does not eliminate the need for permanent operational controls. Integrating regulatory classification, fire load analysis, and field observations provides a broader understanding of fire safety conditions.

Downloads

Download data is not yet available.

Metrics

Metrics Loading ...

References

Drysdale, D. (2011). An introduction to fire dynamics (3rd ed.). Wiley.

Hurley, M. J., Gottuk, D. T., Hall, J. R., Jr., Harada, K., Kuligowski, E. D., Puchovsky, M., Torero, J. L., Watts, J. M., Jr., & Wieczorek, C. J. (Eds.). (2016). SFPE handbook of fire protection engineering (5th ed.). Springer.

International Organization for Standardization. (2015). ISO 9001:2015 quality management systems—Requirements. ISO.

International Organization for Standardization. (2018). ISO 45001:2018 occupational health and safety management systems—Requirements with guidance for use. ISO.

Liu, F., Zhao, S., Weng, M., & Liu, Y. (2017). Fire risk assessment for large-scale commercial buildings based on structure entropy weight method. Safety Science, 94, 26–40. https://doi.org/10.1016/j.ssci.2016.12.009

National Fire Protection Association. (2020). NFPA 557: Standard for determination of fire loads for use in structural fire protection design. NFPA.

National Fire Protection Association. (2022). NFPA 10: Standard for portable fire extinguishers. NFPA.

National Fire Protection Association. (2024). NFPA 72: National fire alarm and signaling code. NFPA.

National Fire Protection Association. (2024). NFPA 101: Life safety code. NFPA.

Secretaría de Economía. (2005). Norma Oficial Mexicana NOM-154-SCFI-2005, Equipos contra incendio—Extintores—Servicio de mantenimiento y recarga. Diario Oficial de la Federación.

Secretaría de Energía. (2012). Norma Oficial Mexicana NOM-001-SEDE-2012, Instalaciones eléctricas (utilización). Diario Oficial de la Federación.

Secretaría del Trabajo y Previsión Social. (2008a). Norma Oficial Mexicana NOM-001-STPS-2008, Edificios, locales, instalaciones y áreas en los centros de trabajo—Condiciones de seguridad. Diario Oficial de la Federación.

Secretaría del Trabajo y Previsión Social. (2008b). Norma Oficial Mexicana NOM-026-STPS-2008, Colores y señales de seguridad e higiene, e identificación de riesgos por fluidos conducidos en tuberías. Diario Oficial de la Federación.

Secretaría del Trabajo y Previsión Social. (2010). Norma Oficial Mexicana NOM-002-STPS-2010, Condiciones de seguridad—Prevención y protección contra incendios en los centros de trabajo. Diario Oficial de la Federación.

Secretaría del Trabajo y Previsión Social. (2011). Norma Oficial Mexicana NOM-031-STPS-2011, Construcción—Condiciones de seguridad y salud en el trabajo. Diario Oficial de la Federación.

Secretaría del Trabajo y Previsión Social. (2024). Norma Oficial Mexicana NOM-017-STPS-2024, Equipo de protección personal—Selección, uso y manejo en los centros de trabajo. Diario Oficial de la Federación.